Publication | Closed Access
Wavelet transform approach to high impedance fault detection in MV networks
35
Citations
9
References
2005
Year
Unknown Venue
Fault DiagnosisEngineeringNetwork AnalysisCondition MonitoringReliability EngineeringMv NetworksSystems EngineeringDiscrete Wavelet CoefficientsWavelet Transform TechniqueElectrical EngineeringComputer EngineeringStructural Health MonitoringHif DetectionPower System ProtectionWavelet TheoryAutomatic Fault DetectionSignal ProcessingFault ManagementFault Detection
Application of wavelet transform technique to high impedance arcing fault detection in distribution networks is presented. Phase displacement between discrete wavelet coefficients calculated for zero sequence voltage and current signals at natural network frequency is tracked. The developed wavelet based HIF detector has been tested with EMTP-ATP generated signals, proving better performance than traditionally used algorithms and methods. The protection method proposed is efficient, robust and may be used for HIF detection independently of the network neutral point grounding mode.