IEEE Transactions on Power Delivery · 1995 · 23 citations · 5 references
EngineeringElectrical EngineeringCircuit TheoryEnergy SystemsPower ElectronicsElectrical TechnologyLighting ElectronicsLoad Reduction StrategiesPower QualityBallastBallast SystemsFluorescent LampsHarmonic DistortionLampsTotal Harmonic DistortionTotal Harmonic Distortion ReductionVoltage Harmonic Distortion
This work presents the results of three stages of research performed on energy-efficient electronic ballasts for T8 fluorescent lamps: (a) laboratory experiments on 1/spl phi/ and 3/spl phi/ configurations, (b) field testing on a building before and after retrofit, and (c) computer simulations of a building, and of an actual 12 kV feeder with residential, commercial, and industrial loads. Some of the results indicate: (1) V/sub THD/ (total harmonic distortion) reduction when magnetic and electronic ballasts are combined, (2) neutral current increase or decrease in 3/spl phi/ electronic-ballasts configurations depending upon its type, and (3) decrease in V/sub THD/ along the modeled feeder for lightand heavy-loads after retrofit, and a "maximum allowable" I/sub THD/ for an electronic ballast for retrofit.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">></ETX>
5
Harmonics from compact fluorescent lamps
R.R. Verderber, O.C. Morse, W.R. Alling · 2002 · 12 citations