A comprehensive harmonic study of electronic ballasts and their effect on a utility's 12 kV, 10 MVA feeder

E. Embriz-Santander, A. Domijan, C. Williams

IEEE Transactions on Power Delivery · 1995 · 23 citations · 5 references

Concepts

Abstract

This work presents the results of three stages of research performed on energy-efficient electronic ballasts for T8 fluorescent lamps: (a) laboratory experiments on 1/spl phi/ and 3/spl phi/ configurations, (b) field testing on a building before and after retrofit, and (c) computer simulations of a building, and of an actual 12 kV feeder with residential, commercial, and industrial loads. Some of the results indicate: (1) V/sub THD/ (total harmonic distortion) reduction when magnetic and electronic ballasts are combined, (2) neutral current increase or decrease in 3/spl phi/ electronic-ballasts configurations depending upon its type, and (3) decrease in V/sub THD/ along the modeled feeder for lightand heavy-loads after retrofit, and a "maximum allowable" I/sub THD/ for an electronic ballast for retrofit.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">&gt;</ETX>