Journal of Hygiene · 1973 · 33 citations · 5 references
MedicineOrthopaedic SurgerySurgeryBacteriologyOrthopedicsVentilationMechanical VentilationOperating Room DesignOperating Room EfficiencyVentilation Performance EvaluationVentilation System DesignVentilation SystemsAirflow MeasurementFlow SystemsHospital VentilationLaminar Flow SystemsVentilation EffectivenessVentilation Efficiency MetricsVentilation Performance Testing
An evaluation has been undertaken of the efficiency of laminar-flow ventilation in operating-rooms in which conventional operating-room clothing was used. It has been demonstrated that velocities in the region of 0.3-0.4 m./sec. will give maximum returns for effort in both down-flow and cross-flow systems. At this velocity the laminar-flow system, in terms of airborne bacteria measured at the wound site, was about 11 times more efficient using horizontal air-flow and 35-90 times more efficient using vertical air-flow than a plenum-ventilated operating-room.
5
CONTROL OF WOUND INFECTION IN A THORACIC SURGERY UNIT
R Blowers, George Mason, K.R. Wallace et al. · The Lancet · 1955 · 126 citations
POST‐OPERATIVE WOUND INFECTION
The Medical Journal of Australia · 1957 · 45 citations
LAMINAR/LINEAR FLOW SYSTEM OF VENTILATION
C. Corey Scott · The Lancet · 1970 · 35 citations
Postoperative wound infection.
PubMed · 1956 · 34 citations
AN EXPERIMENTAL LAMINAR-FLOW OPERATING-ROOM
W. Whyte, B. H. Shaw, R. F. W. Barnes · The Lancet · 1971 · 13 citations