2002 · 15 citations · 0 references
ArchitectureMechanical EngineeringAir ConditioningHeat TransferHvac SystemsAir Conditioning EquipmentAir Conditioning SystemsHeat PumpsHumidity EffectsRefrigerationRefrigeration SystemsAir Conditioning EfficiencyAir Conditioning PerformanceEnthalpyHeat Pump SystemsHeat Pump TechnologyMoistureSystem Performance AssessmentSystem Performance Modeling
Tests were conducted at the University of Florida's Solar Energy and Energy Conversion Laboratory (SEECL) to determine the effect of the moisture on the performance of a 3 ton residential heat pump system with R-22 as the working fluid. The performance of the heat pump system was tested in accordance with the ARI Standard 210/240 (ARI 1989) and ANSI/ASHRAE-37-1988 for testing unitary equipment. ASHRAE's "Air Enthalpy Method" was used to determine the performance of heat pump system and ASHRAE's condition "A" [Outside 95/spl deg/F DBT/75/spl deg/F WBT; Inside 80/spl deg/F DBT/67/spl deg/F WBT] was maintained for the tests. The experimental data reveals that moisture levels of approximately 700 ppm in the refrigerant can decrease the system performance by 10-15%. Approximately 50-60% of the moisture injected into the system remains in the refrigerant and the rest mixes with the compressor oil. Hence, it is possible that over a period of time the moisture in the compressor oil may breakdown at the prevailing temperatures and pressures to form acids which may result in catastrophic failure.