An experimental investigation of the effect of moisture on the performance of an air-conditioning system

D. Yogi Goswami, Gursaran D. Mathur, S. N. Gupta, L. Stoff, F. Colacino

2002 · 15 citations · 0 references

Concepts

Abstract

Tests were conducted at the University of Florida's Solar Energy and Energy Conversion Laboratory (SEECL) to determine the effect of the moisture on the performance of a 3 ton residential heat pump system with R-22 as the working fluid. The performance of the heat pump system was tested in accordance with the ARI Standard 210/240 (ARI 1989) and ANSI/ASHRAE-37-1988 for testing unitary equipment. ASHRAE's "Air Enthalpy Method" was used to determine the performance of heat pump system and ASHRAE's condition "A" [Outside 95/spl deg/F DBT/75/spl deg/F WBT; Inside 80/spl deg/F DBT/67/spl deg/F WBT] was maintained for the tests. The experimental data reveals that moisture levels of approximately 700 ppm in the refrigerant can decrease the system performance by 10-15%. Approximately 50-60% of the moisture injected into the system remains in the refrigerant and the rest mixes with the compressor oil. Hence, it is possible that over a period of time the moisture in the compressor oil may breakdown at the prevailing temperatures and pressures to form acids which may result in catastrophic failure.