IEEE Transactions on Power Delivery · 2009 · 49 citations · 11 references
EngineeringElectrical EngineeringCircuit TheoryDifferential EquationsPower ElectronicsCurrent-voltage CharacteristicsPower QualityProtection SystemsTransmission LinesTransmission SystemsComparative EvaluationCurrentsDifferential ProtectionDistortionsPeriodic Signal AnalysisTransmission Line AnalysisTransmission Line Power FlowTransmission Line Theory
We propose a new approach to current differential protection of transmission lines. In this approach, we transform the instantaneous line current(s) by using a moving window averaging technique. If the time span of moving window is equal to one-cycle time, then the steady-state value of the transformed current is zero for a periodic signal which is composed of fundamental and harmonic frequencies. Signal distortions (e.g., a fault) cause the transformed currents to deviate from the nominal zero value. This permits the development of a sensitive, secure, fast, and yet simple current differential protection scheme. The scheme can be applied in toto to series-compensated transmission lines. Results on a four-machine ten-bus system and comparative evaluation with state-of-the-art methods brings out promise of the proposed method.
11
A Current Differential Relay for a 1000-kV UHV Transmission Line
Zhuang Xu, Zhiqiang Du, Li Ran et al. · IEEE Transactions on Power Delivery · 2007 · 117 citations