IEEE Transactions on Power Delivery · 2009 · 705 citations · 23 references
EngineeringElectrical EngineeringCircuit TheoryCritical Infrastructure ProtectionPower ElectronicsDc-dc ConvertersMicrogridsProtection SystemsVoltage RegulationBidirectional Power ConvertersCurrent LimitingFault ProtectionFault Protection SystemsGroundingMicrogrid ProtectionPower System ProtectionProtection Circuits
LV DC microgrids interconnect distributed resources and sensitive loads, but unlike conventional DC systems that use grid‑connected rectifiers with current‑limiting, they are linked to AC grids via bidirectional converters, necessitating a distinct protection design. The paper proposes a design for LV DC microgrid protection and presents the operating principles and technical data of available and emerging protection devices. The authors present device principles, discuss fault‑detection and grounding methods, and evaluate their impact on LV DC microgrids through simulation studies. Available devices can protect LV DC microgrids, though high‑impedance ground faults pose detection challenges.
In this paper, a low-voltage (LV) DC microgrid protection system design is proposed. The LV DC microgrid is used to interconnect distributed resources and sensitive electronic loads. When designing an LV DC microgrid protection system, knowledge from existing DC power systems can be used. However, in most cases, these systems use grid-connected rectifiers with current-limiting capability during DC faults. In contrast, an LV DC microgrid must be connected to an AC grid through converters with bidirectional power flow and, therefore, a different protection-system design is needed. In this paper, the operating principles and technical data of LV DC protection devices, both available and in the research stage, are presented. Furthermore, different fault-detection and grounding methods are discussed. The influence of the selected protection devices and grounding method on an LV DC microgrid is studied through simulations. The results show that it is possible to use available devices to protect such a system. Problems may arise with high-impedance ground faults which can be difficult to detect.
23
Nikos Hatziargyriou, Hiroshi Asano, Reza Iravani et al. · IEEE Power and Energy Magazine · 2007 · 2.5K citations · Full text