High resistance grounding of low voltage systems: a standard for the petroleum and chemical industry

John P. Nelson, P.K. Sen

1996 · 57 citations · 7 references

Concepts

TL;DR

Grounding of low‑voltage (480–600 V) power systems in the petroleum and chemical industry has long been debated, with reliability, continuity of service, and safety concerns rising as system size increases. This paper reviews the history of low‑voltage grounding and evaluates the suitability of ungrounded, solidly grounded, and high‑resistance grounded systems for the industry. It discusses the benefits and limitations of each grounding scheme and analyzes design, construction, operation, and maintenance factors for high‑resistance grounded systems. High‑resistance grounded LV systems are advantageous and should become the industry standard, reserving solidly grounded systems for cases where high‑resistance grounding is impractical.

Abstract

A debate has existed in the petroleum and chemical industry for years concerning the grounding of LV (480-600 V) power systems. Since reliability and continuity of service are important in the petrochemical industry, some engineers in the past preferred using an ungrounded system. The practicality of such ungrounded systems becomes questionable as the size and extent of coverage increases. This paper begins with a brief history of low voltage grounding which includes ungrounded, solidly grounded and resistance grounded systems. As part this discussion, benefits and limitations of each system are covered. Reliability, continuity of service and personnel safety are important issues and are discussed. It is shown that the use of high resistance grounded LV power systems makes good sense in the petrochemical industry. Design, construction, operation and maintenance factors for high resistance grounded power systems are discussed and analyzed. The use of a high resistance grounded power system when three-phase, four-wire loads are present is discussed, Finally, operational problems and solutions are discussed where significant variable speed drive loads are utilized. The use of a high-resistance grounded power system provides so many benefits that it should become a standard of the industry, and the solidly grounded power system should be used only in applications where the high resistance grounded system becomes impractical.

References

7