2004 · 20 citations · 9 references
EngineeringElectrical EngineeringCircuit TheoryElectric Vehicle EngineeringPower ElectronicsPower QualityVoltage RegulationRoot Function
This paper presents a new definition of voltage sag duration which takes into consideration of the voltage tolerance characteristics of individual electrical equipment. The magnitude and the duration of voltage sag are important parameters which characterize the voltage sag event. The conventional voltage sag characterizing method can overestimate the voltage sag in case of non-rectangular sag. Furthermore, it does not take the voltage tolerance characteristics of each equipment into account. Therefore the proposed method in this paper utilizes the minimum voltage (V/sub min/) of voltage tolerance curve of each equipment. The voltage sag profile is approximated with the k/sup th/ radical root function and the effective duration is newly defined considering the voltage tolerance characteristics. The new voltage sag duration is applied to the non-rectangular sag originated from induction motor starting and compared to the maximum time(t/sub max/) to determine whether the voltage sag event can affect the equipment or not.
9
Electrical power systems quality
M. McGranaghan, R.C. Dugan, H. Wayne Beaty · Choice Reviews Online · 1996 · 2.6K citations · Full text
Voltage Sags in Three-Phase Systems
Math Bollen · IEEE Power Engineering Review · 2001 · 112 citations
Engineering, Electrical Engineering, Mechanical Engineering +14
Trends in Power Quality Monitoring
J.A. Parle, M. Madrigal · IEEE Power Engineering Review · 2001 · 87 citations