2006 · 13 citations · 2 references
EngineeringCivil EngineeringElectrical EngineeringBuilding DiagnosticsConstruction EngineeringConstruction TechnologyElectrical MeasurementElectrical MetrologyThree-phase CircuitsExperimental Results InterpretationPartial DischargePartial Discharge Detection
This paper deals with partial discharge measurement on three phase construction. It was shown that the measurement must be conducted on all phases simultaneously to obtain measurement result of partial discharge occurring in whole region of three phase construction with high sensitivity and to obtain information of the partial discharge location. Partial discharge from artificial defect was measured. Experimental results showed some special characteristics of partial discharge in three phase construction. These results were discussed with considering electric field characteristic in three phase construction and coupling capacitance between three phase conductors and between the conductors and the tank.