IEEE Transactions on Power Delivery · 2002 · 91 citations · 6 references
EngineeringElectrical EngineeringCircuit TheoryEnergy SystemsPower ElectronicsActive FiltersConverter TopologiesDc-ac InvertersPower QualityPower System StabilityVoltage RegulationDynamic Voltage RestorationDynamic Voltage RestorerFilter DesignInverter SystemsInvertersLoading EffectPower Converter DesignVoltage Source Inverters
The role of the inverter-side filter used in the dynamic voltage restorer (DVR) is examined. Using circuit analysis method, it is shown that the selection of the filter parameters can affect the DVR inverter rating. Furthermore, with the DVR filter-series injection transformer combination, the loading effect of the filter on the restorer and the primary supply system has been quantified under normal as well as voltage sag conditions. A systematic filter design method is then proposed, the primary objective of which is to achieve specific harmonic performance while ensuring that the DVR inverter rating and the loading effect are minimized. Illustrative examples are also included.
6
N.G. Hingorani · IEEE Spectrum · 1995 · 692 citations
Engineering, Electrical Engineering, Systems Engineering +17
Harmonic Reduction In Group-Connected Generators-HVDC Convertor
J. Arrillaga, C.S. Crimp, M. Villablanca · 2005 · 365 citations
Power supply quality improvement with a dynamic voltage restorer (DVR)
T. Wunderlin, O. Amhof, P. Dahler et al. · 2002 · 50 citations
Engineering, Computer Engineering, Electrical Engineering +16