IEEE Transactions on Power Delivery · 2008 · 73 citations · 6 references
EngineeringCommunicationElectrical EngineeringCircuit TheoryElectromagnetismPower ElectronicsElectrical MeasurementOhm's LawPower QualityTransmission LinesAttenuation ConstantCharacteristic ImpedanceExperimental Study DesignSimplified ModelsTransmission Line AnalysisTransmission Line ModelingTransmission Line Theory
The aim of this paper is to illustrate the development of a theoretical and experimental study on the characterization of medium voltage (MV) cables in the frequency range 25-200 kHz. Two transmission line configurations, line-ground and line-line, were considered in order to evaluate the main parameters, such as the characteristic impedance and the attenuation constant alpha. A simplified model of the line-ground configuration is proposed which allows one to evaluate the characteristic impedance and the attenuation constant by means of geometrical dimensions. The model was verified by experimental measurements on commonly used MV cables, RG7H1R, with an aluminium core of different sections, 95 mm <sup xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">2</sup> and 185 mm <sup xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">2</sup> . Moreover, the experimental tests were carried out for the line-line configuration.
6