IEEE Transactions on Energy Conversion · 2005 · 44 citations · 12 references
EngineeringElectrical EngineeringCircuit TheoryElectric MachinesPower ElectronicsElectrical System DiagnosticsFault DetectionGenerator OperationMachine WindingsPower Grid AnalysisSynchronous MachinesDynamic Transient BehaviorPower System Fault TransientsSalient Pole Synchronous MachinesStator Winding FaultsStator WindingsSynchronous Generator OperationSynchronous Machine Modeling
An improved model for simulating the transient behavior of salient-pole synchronous generators with internal and ground faults in the stator winding is established using the multi-loop circuit method. The model caters for faults under different ground conditions for the neutral, and accounts for the distributed capacitances of the windings to ground. Predictions from the model are validated by experiments, and it is shown that the model accurately predicts the voltage and current waveforms under fault conditions. Hence, it can be used to analyze important features of faults and to design appropriate protection schemes.
12