Several methods have been developed so far which attempt to detect leaks in water distribution systems by taking into account pressure (and possibly other available) measurements. As in many previous approaches, the leak detection problem is formulated and solved here as an inverse problem with unknown leak areas being the calibration parameters. However, unlike the previous approaches, a stochastic (rather than deterministic) leakage detection methodology is developed and used here. This methodology is based on the Shuffled Complex Evolution Metropolis (SCEM-UA) algorithm and is capable of estimating the posterior probability density functions of unknown leak areas in a single model run. Baring in mind the accuracy of similar leak detection approaches, it is believed that the stochastic context used here is more appropriate than the deterministic one used before. To achieve the above goal, the Epanet2 hydraulic network modelling software is linked to the SCEM-UA software in the Matlab programming environment. The SCEM-UA algorithm parameters are tuned to achieve an effective and efficient search for unknown leak areas. The methodology developed is tested on two literature case studies. This paper was presented at the 8th Annual Water Distribution Systems Analysis Symposium which was held with the generous support of Awwa Research Foundation (AwwaRF).