IEEE Transactions on Industry Applications · 1992 · 26 citations · 6 references
EngineeringElectrical EngineeringIndustrial EngineeringAutomationPower ElectronicsProcess ControlElectrical System DiagnosticsElectrical TechnologyPower QualityPower SystemsVoltage RegulationCurrent Harmonic DistortionHarmonic DistortionHarmonic EffectsHarmonic MitigationHarmonicsRelay ProtectionRelaysVoltage Harmonic Distortion
The results of a study on the effects of voltage and current harmonics on the operation of four types of solid-state relays (SSRs) used in control schemes of many industrial applications are presented. This study started after repeated malfunctions of electrophotographic printers in some data processing centers. The misoperation of zero-switching SSRs was suspected as the cause of the malfunction. Tests on the SSRs were performed using a single-phase harmonic generator and a LeCroy digital oscilloscope with signal processing software capabilities. The results reported indicate that voltage harmonic distortion may cause a delay in the turn-on time of more than a cycle. In some cases, complete failure to turn on or off may occur. Recommendations based on academic research, user's experience, and manufacturers viewpoints are given.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">></ETX>
6
Harmonic Reduction In Group-Connected Generators-HVDC Convertor
J. Arrillaga, C.S. Crimp, M. Villablanca · 2005 · 365 citations