The transient behavior of the standby diesel-generator units and the engineered safeguard loads at an operating nuclear power generating station was simulated using the electromagnetic transients program (EMTP). The authors discuss the standby diesel-generator units and the engineered safeguard load model development and the validation and verification of the applicable EMTP modules. The simulation results demonstrating the standby diesel-generator unit capability and illustrating the predicted transient deviations in the generator terminal voltage and frequency are included together with the voltage deviations within the engineered safeguard features distribution system.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">&gt;</ETX>