Publication | Closed Access
Hybrid Cascaded H-bridge Converter for Harmonic Current Compensation
48
Citations
26
References
2012
Year
Electrical EngineeringEngineeringActive FilterPower Electronics ConverterDelta ConfigurationElectric Power ConversionPower InverterPower ElectronicsH-bridge ConvertersHarmonic MitigationH-bridge ConverterActive Power Filter
This paper describes a three-phase trasformerless active filter system based on hybrid cascaded H-bridge converters with delta configuration. It is intended for dynamically compensating harmonic current of three-phase nonlinear load. This active filter is characterized by per-phase series connection of a high-voltage converter operating at 50 Hz and a low-voltage converter operating at 7.5 kHz. DC-link voltages of all converters are regulated purely by control algorithm without any auxiliary circuit. The dc voltage ratio of 2:1 is realized for the series-connected converters by injecting zero-sequence current with fundamental, third-harmonic, and fifth-harmonic components to the three clusters. An experimental prototype rated at 100 V and 1 kVA is built up in authors' lab. Experiment results confirm the validity of this dc voltage control method and harmonic current compensation capability.
| Year | Citations | |
|---|---|---|
Page 1
Page 1