IEEE Transactions on Power Delivery · 1995 · 280 citations · 9 references
ComputingComputer ScienceElectrical EngineeringComputer NetworksCritical Infrastructure ProtectionMachine LearningFault DetectionFault DiagnosisProtection SystemsArc Fault DetectionAutomatic ReclosingMachine Learning For Fault DetectionNeural Network-based DiagnosisParallel TransmissionProtection RelayingProtective RelayingRelay Protection
This paper presents a new approach to fault classification for high speed protective relaying and show its effectiveness in computer simulations on parallel transmission lines. The scheme is based on the use of neural network architecture and implementation of digital signal processing concepts. We begin by classifying several fault types like 1-phase-to-ground, 2-phase-to-ground and 3-phase-to-ground faults. We proceed with classification of arcing and nonarcing faults in order to obtain a successful automatic reclosing. Encouraging results are shown and indicate that this approach can be used for supporting a new generation of very high speed protective relaying systems.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">></ETX>
9