2011 · 14 citations · 6 references
EngineeringElectrical EngineeringOptoelectronicsPower ElectronicsVisual PsychophysicsElectrical System DiagnosticsElectrical System TestingLighting ElectronicsLighting QualityLighting StandardsPower QualityFlickerFlicker ControlFlicker DetectionLampsLight Flicker EffectsLighting Performance MonitoringSystem TestingVoltage
The paper is focused on evaluation of flicker produced by various lamp types as consequence of a Ripple Control Signal (RCS) presence in supply voltage. On the basis of observations the resulting flicker severity differs from values measured according to the EN 61000-4-15 standard and moreover is very variant; depending i.a. on the RCS parameters and on the lamp type used in installation. Considering that the RCS transmitted as telegram carrying information (command) is generally a periodical signal, a specialized testing system utilizing a light flickermeter has been developed and used for the flicker severity assessment and obtained results “objectively” comparing measured lamps response are presented in the paper.
6