2007 · 410 citations · 7 references
EngineeringElectrical EngineeringEnergy SystemsLow-power DesignPower ElectronicsConverter TopologiesDistributed Energy ResourcesPower ManagementPower System DesignPower SystemsData Center CoolingData Center Energy OptimizationEnergy-efficient DistributionPower ConversionPower Conversion EfficiencyPower Delivery EfficiencyPower DistributionPower Grid Design
In a typical data center, less than half the energy consumed is delivered to the compute load, with the rest lost in power conversion, distribution and cooling. Traditionally power distribution is at 400/480 V AC in data centers and at -48 V DC in telco facilities. Higher voltage DC has been proposed as an energy efficient distribution option for both types of facilities, and this paper presents an analytical evaluation of several data center power delivery architectures over a range of loads, showing that a 400 V facility-level DC distribution option is the most efficient. The equipment required to support such an architecture is discussed and results from a small scale demonstration are included.
7
New power supply optimised for new telecom networks and services
Didier Marquet, Fernando Miguel, A. Deshayes et al. · 1999 · 18 citations
Total DC Integrated Data Centers