IEEE Transactions on Plasma Science · 2007 · 34 citations · 2 references
EngineeringElectrical EngineeringPhysicsElectromagnetismMicroelectronicsPower ElectronicsCurrent-voltage CharacteristicsElectric CircuitsElectric PotentialBreakdown CharacteristicsBreakdown VoltageCircuit Breaker ReliabilityContact MaterialsElectrode Surface StructureVoltage Interruption
To realize the high-voltage vacuum circuit breaker, we investigated the voltage-distribution ratio after current interruption at the double-break vacuum circuit breaker. We used the spiral CuCr (20%) electrodes and the axial magnetic-field CuCr (50%) electrodes as the experimental electrodes. At the double-break vacuum circuit breaker, where two vacuum interruptions that had the same and different characteristics of the electrode structure and contact materials were connected in series, there was a bias in the voltage-distribution ratio of each vacuum interrupter after current interruption. This seems to be because there was difference in the postarc current that passed through each vacuum interrupter after current interruption.
2
Post Arc Current of Vacuum Interrupters
S. Yanabu, M. Homma, E. Kaneko et al. · IEEE Transactions on Power Apparatus and Systems · 1985 · 72 citations
Post Arc Current in Vacuum Interrupters
S. Yanabu, Y. Satoh, Mareki Honma et al. · IEEE Transactions on Power Delivery · 1986 · 40 citations