Withstand Voltage Characteristics of Two Series Vacuum Interrupters

Yuji Shiba, Naotaka Ide, Hiroki Ichikawa, Yoshihiko Matsui, Masayuki Sakaki, S. Yanabu

IEEE Transactions on Plasma Science · 2007 · 34 citations · 2 references

Concepts

Abstract

To realize the high-voltage vacuum circuit breaker, we investigated the voltage-distribution ratio after current interruption at the double-break vacuum circuit breaker. We used the spiral CuCr (20%) electrodes and the axial magnetic-field CuCr (50%) electrodes as the experimental electrodes. At the double-break vacuum circuit breaker, where two vacuum interruptions that had the same and different characteristics of the electrode structure and contact materials were connected in series, there was a bias in the voltage-distribution ratio of each vacuum interrupter after current interruption. This seems to be because there was difference in the postarc current that passed through each vacuum interrupter after current interruption.

References

2