OPTIMAL PLACEMENT AND UTILIZATION OF PHASOR MEASUREMENTS FOR STATE ESTIMATION

Bei Xu, Yeo Jun Yoon, Ali Abur

2005 · 99 citations · 4 references

Concepts

Abstract

Abstract – This paper presents a procedure by which new PMU locations can be systematically determined in order to render an observable system. The procedure is then extended to account for cases of loss of a single phasor measurement unit (PMU). Buses with zero and non-zero injections, and branches with power flow meas-urements are also accounted for in this generalized proce-dure. Several cases involving different power system and measurement configurations are presented where intro-ducing few extra strategically placed PMUs minimizes vulnerability of the measurement system against the loss of single PMUs. The paper also develops a linear estimator based on strictly PMU measurements and investigates the computational performance as well as the bad data proc-essing problem. Detection and identification of PMU fail-ures are demonstrated via simulations.

References

4