Impact Research of Inductive FCL on the Rate of Rise of Recovery Voltage With Circuit Breakers

Qingmin Li, Hongshun Liu, Jie Lou, Liang Zou

IEEE Transactions on Power Delivery · 2008 · 34 citations · 7 references

Concepts

Abstract

Fault current limiter (FCL) is expected to ease the burden on circuit breakers by limiting the fault current to a desired level. However, the burden on the circuit breakers depends not only on the interrupting current but also on the rate of rise of recovery voltage (RRRV). Based on an equivalent model of the inductive FCL and with respect to FCL terminal fault and short-line fault respectively, strict mathematical formula are presented to describe the relationship between the RRRV and the current limit factor, the stray capacitance as well as the short-line fault distance. Further, detailed computations were carried out regarding a 220-kV transmission line with three-phase-to-ground faults to fully account for the concrete impacts on the RRRV from key influential factors. The calculation results by the proposed theoretical formula in this paper coincide well with the simulations in some previous publications. The specific investigation presents analytical basis and theoretical reference for optimal parameter design of inductive FCLs and reliable selection of the interrupting characteristics of HV circuit breakers.

References

7