ISRN Chemical Engineering · 2013 · 13 citations · 13 references
EngineeringMechanical EngineeringPhysicsFluid DynamicsHeat TransferThermal AnalysisHeat ExchangeHeat ExchangersHeat FlowHeat Transfer AnalysisHeat Transfer FundamentalsLaminar FlowFluid-thermal CouplingHeat Exchanger PerformanceLaminar Flow Heat TransferLaminar Flow RegimesNusselt NumberPressure DropReynolds NumberShell-and-tube Heat Exchangers
In this study, the experimental analysis was performed on the shell-and-tube type heat exchanger containing segmental baffles at different orientations. In the current work, three angular orientations (<mml:math xmlns:mml="http://www.w3.org/1998/Math/MathML" id="M1"><mml:mrow><mml:mi>θ</mml:mi></mml:mrow></mml:math>) 0°, 30°, and 60° of the baffles were analyzed for laminar flow having the Reynolds number range 303–1516. It was observed that, with increase of Reynolds number from 303 to 1516, there was a 94.8% increase in Nusselt number and 282.9% increase in pressure drop. Due to increase of Reynolds number from 303 to 1516, there is a decrease in nondimensional temperature factor for cold water (<mml:math xmlns:mml="http://www.w3.org/1998/Math/MathML" id="M2"><mml:mrow><mml:mi>ω</mml:mi></mml:mrow></mml:math>) by 57.7% and hot water (<mml:math xmlns:mml="http://www.w3.org/1998/Math/MathML" id="M3"><mml:mrow><mml:mi>ξ</mml:mi></mml:mrow></mml:math>) by 57.1%, respectively.
13