Prevention of high-fault rupture of pole-type distribution transformers

W.R. Mahieu

IEEE Transactions on Power Apparatus and Systems · 1975 · 48 citations · 0 references

Concepts

Abstract

Violent rupture of distribution transformers has occurred with increasing frequency in recent years. The problem appears greatest with pole-type units at locations with high available short-circuit currents. This paper concerns the rupture of pole-type distribution transformers subjected to internal, submerged, arcing faults of high current magnitude. An analysis of a probable rupture process and tests of faulted transformers were used to obtain a simple semi-empirical equation for the internal transformer pressure rise. Limiting the I <sup xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">2</sup> t during the fault with current limiting fuses is shown to be a practical means of minimizing the probability of transformer rupture.