IEEE Power Engineering Review · 2002 · 63 citations · 7 references
EngineeringElectrical EngineeringElectromagnetismGeomagnetismPower ElectronicsElectrical System DiagnosticsMagnetic StormsPower Grid AnalysisPower QualityProtection SystemsVoltage RegulationCurrent Distribution AnalysisGeomagnetically Induced CurrentsProtection CircuitsReactive Power CompensationReactive Power ControlTransformer ProtectionVoltageVoltage Control
The geomagnetic induced currents in a transmission network may saturate transformers and cause additional losses, a high level of harmonics, and a lack of reactive power in the grid. Malfunctioning of protection circuits is also reported in the literature. The field tests made for two 463 MVA system transformers show that tested transformers may tolerate very high dc currents for times typical to geomagnetic storms. The effects for the voltage control and voltage quality in network are also considered and results of earlier Finnish GIC risk studies are reported.
7