IEEE Transactions on Power Systems · 2005 · 59 citations · 8 references
EngineeringElectrical EngineeringCircuit TheoryPower ElectronicsRenewable Energy IntegrationNodal AnalysisPower Grid AnalysisPower System DesignPower SystemsPower Transmission SystemsTransmission LinesDecouplingElectrical Network ModelingLoad Flow AnalysisPower Flow AnalysisPower System ModellingTransmission Line LossesTransmission Line Power FlowTransmission Losses
In this paper, a modification of the topological generation load distribution factor method of power flow tracing is reported. The modification is needed since the existing method introduces additional fictitious nodes on system lines in order to take into account the transmission losses. Due to the expansion of a system, the existing algorithm based on the augmented matrix equation requires more mathematical effort and memory and longer calculation time to obtain a solution. The new approach successfully avoids the matrix expansion by introducing matrix decoupling, which is its main improvement. The second novelty is an introduction of an equivalent model of a line that unites the nodal reactive power with the power produced by shunt admittances. Thus, the modified method can be also applied to the reactive power flows and transmission-loss allocation.
8