Power quality and factory automation

Van Wagner, A.A. Andreshak, J.P. Staniak

IEEE Transactions on Industry Applications · 1990 · 115 citations · 4 references

Concepts

Abstract

A case study involving monitoring power quality disturbances at a representative plant and identifying the disturbances that disrupt production is described. The sensitivities of representative electronic control equipment to the identified disturbances were measured and then projected to form a plant disturbance threshold. For the monitoring effort, six disturbance analyzers were installed at four voltage levels extending from the utility 40 kV station to 120 V control power in an individual machine tool. Voltage sags were the only disturbance to directly cause lost production and were the most common disturbance at 68% of the total number of events recorded. Two programmable logic controller (PLC) transfer lines and a computerized numerically controlled (CNC) lathe were tested with a sag generator to determine the sensitivities of the equipment. The most sensitive components required the voltage during a sag to drop to less than 80-86% of rated to malfunction, whereas the least sensitive required the voltage to drop below 30% of rated. From the test results, the calculated sag threshold at the utility feed to the plant to disrupt production was 87% of the nominal voltage for more than 8.3 ms.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">&gt;</ETX>