Behavior of induction motor due to voltage sags and short interruptions

M.M. Morcos, C. Reineri, G. Campetelli

IEEE Transactions on Power Delivery · 2002 · 113 citations · 17 references

Concepts

Abstract

An experimental study and some calculations on induction motor behavior were carried out. The effects due to short interruptions and voltage sags were investigated. A standard three-phase squirrel-cage motor of 5.5 kW, 1500 r/min, and 380 V was used. The presence of induction motor changes the voltage sag waveform and duration. Protection characteristic curves and contactor ride-through capability together with their improvement are also studied. The interaction between motor load, system hot-load pickup, and voltage sag magnitude determine the motor re-acceleration duration and magnitudes. Besides, on-sag and post-sag currents can reach levels higher than the direct start values. Post-sag overcurrent duration can last more than twice the normal start time period, having specific energies in the same order of magnitude.

References

17