Considerations of a shunt active filter based on voltage detection for installation on a long distribution feeder

Keiji Wãda, Hideaki Fujita, Hirofumi Akagi

IEEE Transactions on Industry Applications · 2002 · 166 citations · 7 references

Concepts

Abstract

This paper deals with a curious phenomenon referred to as the "whack-a-mole" that may occur in a long-distance distribution feeder having many capacitors for power-factor correction. The idea of whack-a-mole is that installation of an active or passive filter on the feeder makes voltage harmonics increase on some buses, whereas it makes voltage harmonics decrease on other buses, especially at the point of installation. The distributed-parameter representation is applied to a simplified feeder, thus making it possible to perform analysis of the whack-a-mole. As a result, this analysis yields such a basic way as to avoid the whack-a-mole. Moreover, both theory and experiment clarify that installation of the active filter acting as a harmonic terminator on the end bus of the feeder can damp out harmonic propagation throughout the feeder without causing any whack-a-mole.