IEEE Transactions on Power Delivery · 2006 · 46 citations · 1 references
Electrical EngineeringEngineeringEye TrackingFlicker PowerElectric Power QualityMonitoring PointSignal ProcessingFlicker Source
This paper describes an algorithm for calculating the direction to a flicker source with respect to a monitoring point. The proposed algorithm is based on sampling of both the voltage and current. The low-frequency fluctuations in voltage and current are recovered from the input signals by demodulation, and passed through a bandpass filter as described in IEC 61000-4-15. A new quantity-flicker power-is defined from the output signals of the two filters. The direction to a flicker source is obtained from the sign of this flicker power. The proposed algorithm has been validated by simulations and several field measurements.
1
Identification of flicker sources
A. Dán · 2002 · 20 citations
Flicker Effect, Optical Information Processing, Same Busbar +3