IEEE Transactions on Magnetics · 1993 · 17 citations · 4 references
Superconducting MaterialElectrical EngineeringEngineeringHigh Voltage EngineeringPower TransformerElectrical TransmissionSuperconductivitySuperconducting WindingsElectric Power TransmissionElectric Power ConversionPower Electronic SystemsPower Electronics330-Kva Power TransformerSuperconducting DevicesPower TransmissionLiquid Helium BathPower Electronic Devices
A 330-kVA power transformer with superconducting windings is discussed. A niobium-titanium based superconducting wire optimized for AC applications was used in the windings. The transformer worked according to its design at rated power. The total heat input to the liquid helium bath at this power was 9.4 W, of which the AC losses dissipated in the windings were about 1 W per winding. The low voltage feedthroughs which had to carry 830 A/sub rms/ at rated power worked adequately. The transformer revealed an apparent current limiting effect. This property can be utilized to limit currents in a network for time periods 10-50 ms. A quench protection device was designed and incorporated in the test circuit.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">></ETX>
4
Reduction of AC losses in ultra-fine multifilamentary NbTi wires
J.R. Cave, A. Février, T. Verhaege et al. · IEEE Transactions on Magnetics · 1989 · 41 citations