Negative impulse flashover along cylindrical insulating surfaces bridging a short rod-plane gap under variable humidity

13

Citations

17

References

2010

Year

Abstract

Negative impulse flashover along insulating surfaces bridging a short rod-plane gap is investigated under variable humidity. The specimens, cylindrical in shape and with a smooth surface, were made of PTFE, silicone-rubber, nylon and glazed porcelain and were bridging the gap, which was stressed by standard lightning and switching impulse voltages. Breakdown probability distributions were obtained and the breakdown voltage and time to breakdown were measured. The gap was overstressed by applying voltages higher than that causing 100% breakdown so as to study the effects of the applied peak voltage on breakdown characteristics. When breakdown occurs over an insulating surface the breakdown voltage is significantly lower compared to that obtained for air alone, especially at lower breakdown probabilities and under switching impulse voltages. It is also lower for lightning than switching impulse voltages, this being less marked with increasing material permittivity. Breakdown is closely related to negative corona growth. The effect of absolute humidity on breakdown voltage is minimal. The IEC atmospheric conditions correction procedure yields satisfactory results when breakdown occurs both in air alone and along an insulating surface.