IEEE Transactions on Power Delivery · 2005 · 54 citations · 9 references
EngineeringElectrical EngineeringPhysicsCircuit TheoryPlasma PhysicsPower ElectronicsPower Distribution ControlPower Grid AnalysisPower QualityVoltage RegulationControl CablesCurrentsElectric Substation ProtectionFrequency Content AnalysisFrequency Spectrum AnalysisOvervoltage TransientsSwitching TransientsTransient Overvoltages
The conducted as well as the induced voltages on control cables and control circuits due to transient electromagnetic (EM) fields generated during switching operations in a gas-insulated substation (GIS) depend on the waveshape of the very fast transient overvoltages and the associated very-fast transient currents (VFTCs). The aim of this paper is to build a basis for characterizing the VFTC generated in gas-insulated switchgear and the associated equipment during switching operations for the study of transient coupling phenomena. The peak magnitudes of VFTC and their dominant frequency content at various locations have been computed in a 245-kV GIS for different switching operations as well as substation configurations. Finally, the influence of the substation layout on the frequency spectrum, dominant frequencies, and the highest possible frequency component of the VFTC at various distances from the switch have been reported.
9
Jan Meppelink, K.J. Diederich, K. Feser et al. · IEEE Transactions on Power Delivery · 1989 · 183 citations
Transient electromagnetic interference in substations