Publication | Closed Access
Blocking of Zone 3 Relays to Prevent Cascaded Events
66
Citations
11
References
2008
Year
EngineeringPower Grid OperationZone 3Network AnalysisResilient Control SystemProtective RelaysControl ProtocolReliability EngineeringSystems EngineeringDistance RelaysPower SystemsNetworked Computer SystemsComputer EngineeringSmart Grid SecurityPower System ProtectionSmart GridPower System ReliabilitySurvivable NetworkCascaded Events
<para xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink"> Defense systems are needed to prevent catastrophic failures of a power grid due to cascaded events. Cascaded events can be attributed to improper operations of protective relays. The most challenging problem for the design and implementation of a defense system is the performance in accuracy and speed in a real-time environment. Protective devices are normally designed to operate fast in order to isolate the fault(s). This paper proposes a new methodology to distinguish line overloads from actual faults for distance relays. In order to distinguish between line flow transfers from a line outage and an actual fault, the line outage distribution factor (LODF) and generation shift factor (GSF)-based power flow estimation method, and a secure peer-to-peer (P2P) communication structure are adopted. Computer simulations of cascaded events for a six-bus system and the Korean power grid have been performed to establish the feasibility of the proposed scheme. </para>
| Year | Citations | |
|---|---|---|
Page 1