The cold-fog test [for outdoor insulators]

William A. Chisholm, K.G. Ringler, C.C. Erven, M.A. Green, O.T. Melo, Y. T. Tam, O. Nigol, J. Kuffel, Alexandre Boyer, I. K. Pavasars,

IEEE Transactions on Power Delivery · 1996 · 69 citations · 9 references

Concepts

Abstract

The electrical performance of outdoor insulation degrades severely during combinations of factors that include surface contamination, ice, fog and an ambient temperature that rises through 0/spl deg/C (T(0/spl deg/)). Failures at operating voltage on 115 kV, 230 kV and 500 kV power systems occur with increasing probability under those conditions. A new CFT(0/spl deg/) or "cold-fog" test method has been developed to reproduce the flashovers at all three voltage levels. Three options are identified for improving CFT(0/spl deg/) performance: use of semi-conductive glazes; substitution of silicone for porcelain; and use of silicone coatings on existing porcelain insulators.