The Indoor Environment in Dwellings: A Study of Air-exchange, Humidity and Pollutants in 115 Danish Residences

Henrik Harving, Ronald E. Dahl, J. Korsgaard, Svend Aage Linde

Indoor Air · 1992 · 22 citations · 11 references

Concepts

Abstract

A total of 115 Danish dwellings were investigated during the winter season in order to evaluate the indoor environment. The sample was considered representative of Danish dwellings. Measurements of air-exchange rates in the bedrm showed a very low natural venthtion with a median air-exchange rate of 0.28 air changes per hour (ach) (interqmmle range (IQR): 0.12 –0.56).18% of the dwellings had a natural air-exchange below a detectable limit of 0.10 ach and 72% had air-exchanges rates below the requirements in Danish Building Codes of 0.50 ach. The investigations showed a statistically signifiant inverse correlation between air-exchange rates and absolute indoor humidity. Concentrations of formaldehyde and volatile organic compounds were measured in 36 dwellings. The median formaldehyde concentration was 0.037 mg/m3 which is well below the recommended indoor TLV The concentration of VOC in some cases reached a level that may be of importance for persons with sensitive airways. It is concluded that natural ventilation in a great number of Danish dwellings is too low fiom a health point of view and that the requirements in Danish Building codes are insufficient to ensure acceptable air-exchange rates.