Identification of Factors That Disrupt Negative Air Pressurization of Respiratory Isolation Rooms

46

Citations

1

References

2000

Year

Abstract

A substantial percentage of IRs did not meet the negative air pressure criterion. These failures were associated with a variety of characteristics in the design and operation of the IRs. Our findings indicate that a balanced ventilation system does not guarantee inward airflow direction. Devices that continuously monitor and, in some cases, control the pressurization of IRs had poor reliability. This study demonstrates the utility of using visible smoke for testing directional airflow of IRs, whether or not continuous monitors are used. Institutional tuberculosis control pro grams should include provisions for appropriate monitoring and maintenance of IR systems on a frequent basis, including the use of visible smoke.