Enhanced signal processing for conventional and unconventional PD measuring methods: Wavelet de-noising, automatic detection algorithms and averaging for arrival time-based PD location in transformers and power cables

Sacha Markalous, Thomas Strehl, C. Herold, Thomas Leibfried

2008 · 12 citations · 5 references

Concepts

Abstract

Two major tasks of partial discharges (PD) measurements may be distinguished, (i) providing general evidence and the type of PD (detection) and (ii) the location of the PD. Dependent on the type of device under test the two issues have changing priority. For the on-line/on-site PD location in power transformers unconventional PD measuring methods like acoustic ultra-sonic measurements or electromagnetic measurements up to the UHF (ultra high frequencies) range are performed, while the Time Domain Reflectometry (TDR) of electric PD signals is a standard technique for the location of PD in power cables.