A survey of generator back-up protection practices: IEEE committee report

G.D. Rockefeller, A. Darlington, W.A. Elmore, Ricardo Fernández, J.R. Gil-Berlinches, Ralph Haas, L. E. Landoll, W. Marsh, George Nail, A. Pierce,

IEEE Transactions on Power Delivery · 1990 · 10 citations · 1 references

Concepts

Abstract

The authors report on and analyze a survey of practices and experiences with time-delay back-up protection associated with unit-connected generators, predominantly rated 100 MVA and above. In addition, application and setting considerations are discussed. The survey covered large unit-connected installations, involving 47 respondents and 6698 unit-years of experience. Phase back-up, negative-sequence overcurrent, and high-side neutral overcurrent protection were considered. The majority of respondents were found to apply all three classes of back-up protection: phase, negative-sequence, and high-side neutral overcurrent.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">&gt;</ETX>