Radiation Protection Dosimetry · 1998 · 26 citations · 0 references
DentistryPreventive MedicineRadiation DosimetryRadiation ProtectionRadiation SafetyBiological Effects Of RadiationOccupational Radiation ProtectionPatient Radiation ProtectionPatient Radiation SafetyRadiation HealthRadiation Risk AssessmentPhillips ModelRadonRadon Background MeasurementRadon ControlRadon MeasurementRadon MonitoringRadon Progeny DetectionRadon Risk Assessment
A series of continuous real-time radon and radon progeny measurements together with passive etched track detector measurements were performed in hospital premises during 1996. In one small room, detailed measurements over several weeks showed that both the radon concentration and the Equilibrium Factor depended on the intermittent operation of a filtered positive pressure displacement air-conditioning system, which was designed to conform to operating theatre standards. The average radon level measured while the air-conditioning was off was almost four times higher than that recorded whilst it was on. The progeny level was over five times higher than that whilst it was on. Thus, the Equilibrium Factor (F), was significantly lower when the air-conditioning was on. Measurements in similar rooms in two hospitals, confirmed that the reduction in radon level was a general finding. Thus staff working in such environments receive significantly lower radiation dose from radon than staff working in nearby normally ventilated rooms.