OSTI OAI (U.S. Department of Energy Office of Scientific and Technical Information) · 1990 · 13 citations · 0 references
EngineeringBuilding ScienceMechanical EngineeringAir ConditioningHeat TransferThermal ComfortAir Conditioning SystemsBuilding Cooling SystemsCooling SystemsEvaporative CoolingThermal DesignThermal ManagementCoolingHeat RecoveryHeat RejectionHeat Rejection SystemsIndirect CoolingIndirect Evaporative CoolingMechanical CoolingProduction Costs
Makeup air semiconductor clean spaces can vary from 1 cfm/ft{sup 2} (5.08 L/s {center dot} m{sup 2}) to 10 cfm/ft{sup 2} (50.81 L/s {center dot} m{sup 2}) and typically averages 5 cfm/ft{sup 2} (25.4 L/s {center dot} m {sup 2}). Accordingly, the energy requirements to cool, dehumidify, preheat, and/or humidify are significant and can represent 30% to 65% of the total thermal energy required to maintain a cleanroom environment. Because of high energy requirements, cost-effective means to reduce energy costs can influence unit production costs. The greatest opportunity for significant energy savings can be achieved by reducing or displacing mechanical cooling or fuel-generated heating requirements. The primary focus of this paper is to present and discuss various concepts of heat recovery, dual-temperature cooling, direct and indirect evaporative cooling, and heat rejection directed toward makeup air systems that can achieve these objectives. In addition, equipment-sizing considerations not necessarily applicable to systems that are less energy intensive or that operate continuously are explored.