Makeup air systems energy-saving opportunities

W. K. Brown

OSTI OAI (U.S. Department of Energy Office of Scientific and Technical Information) · 1990 · 13 citations · 0 references

Concepts

Abstract

Makeup air semiconductor clean spaces can vary from 1 cfm/ft{sup 2} (5.08 L/s {center dot} m{sup 2}) to 10 cfm/ft{sup 2} (50.81 L/s {center dot} m{sup 2}) and typically averages 5 cfm/ft{sup 2} (25.4 L/s {center dot} m {sup 2}). Accordingly, the energy requirements to cool, dehumidify, preheat, and/or humidify are significant and can represent 30% to 65% of the total thermal energy required to maintain a cleanroom environment. Because of high energy requirements, cost-effective means to reduce energy costs can influence unit production costs. The greatest opportunity for significant energy savings can be achieved by reducing or displacing mechanical cooling or fuel-generated heating requirements. The primary focus of this paper is to present and discuss various concepts of heat recovery, dual-temperature cooling, direct and indirect evaporative cooling, and heat rejection directed toward makeup air systems that can achieve these objectives. In addition, equipment-sizing considerations not necessarily applicable to systems that are less energy intensive or that operate continuously are explored.