IEEE Transactions on Power Delivery · 1999 · 88 citations · 3 references
EngineeringElectrical EngineeringCircuit TheoryElectromagnetismPower ElectronicsMagnetic Circuit AnalysisMagnetic ComponentsThree-phase CircuitsCurrent Harmonic DistortionHarmonic DistortionHarmonicsPhase SequenceThree-phase Circuit ModelingThree-phase TransformersTotal Harmonic DistortionTransformer Theory
This paper proposes a new model for three-phase transformers with three legs with and without task under DC bias based on electric and magnetic circuit theory. For the calculation of the nonsinusoidal no-load currents, a combination of time and frequency domains is used. The analysis shows that (1) asymmetric three-phase transformers with three legs generate magnetizing currents with triplen harmonics not being of the zero-sequence type. (2) The wave shapes of the three magnetizing currents of (asymmetric) transformers are dependent on the phase sequence. (3) The magnetic history of transformer magnetization-due to residual magnetization and hysteresis of the tank-cannot be ignored if a DC bias is present and the magnetic influence of the tank is relatively strong, e.g., for oil-cooled transformers. (4) Symmetric three-phase transformers with three legs generate no-load currents without triplen harmonics. (5) The effects of DC bias currents (e.g., reactive power demand, harmonic distortion) can be suppressed employing symmetric three-phase transformers with three legs including tank. Measurements corroborate computational results; thus this nonlinear model is valid and accurate.
3
Reactive Power Demand of Transformers with DC Bias
Y. You, E.F. Fuchs, D. Lin et al. · IEEE Industry Applications Magazine · 1996 · 41 citations