A Practical Approach for Determining the Ground Resistance of Grounding Grids

Guemes-Alonso, F.E. Hernando-Fernandez, F. Rodriguez-Bona, J.M. Ruiz-Moll

IEEE Transactions on Power Delivery · 2006 · 49 citations · 19 references

Concepts

TL;DR

Ground resistance is independent of earth‑fault current, and knowing it allows calculation of grid potential and touch‑and‑step voltages. The study aims to develop a finite‑element method and derive a simple equation for calculating the ground resistance of grounding grids in uniform soils. The authors use a finite‑element approach, validate it against experimental measurements and literature data, and then use the results to formulate an easy‑to‑use equation. The method accurately matches experimental and literature results, enabling fast, accurate analysis of symmetrical and nonsymmetrical grids of any shape in uniform soils.

Abstract

This paper starts from the premise that ground resistance is independent of earth-fault current and presents a new method for calculating the ground resistance of grounding grids using the finite-element method. The results obtained using the method proposed are compared with results measured experimentally and results published by other authors. Once ground resistance and earth-fault current are known, grid potential and touch-and-step voltages can be calculated. The main advantage of the method proposed here is that it permits us to analyze symmetrical and nonsymmetrical grids of any shape in uniform soils. It provides a fast-resolution industrial application with acceptable results for calculating the ground resistance of grounding grids of any shape. The results obtained with the proposed method are used as the basis for formulating an easy-to-use equation for calculating the ground resistance of grounding grids in uniform soils.

References

19