IEEE Transactions on Power Systems · 2011 · 180 citations · 23 references
EngineeringElectrical EngineeringSystems EngineeringCircuit TheoryInfrastructure Systems AnalysisPower ElectronicsElectrical System TestingPower Grid AnalysisPower QualityPower System StabilityPower SystemsThevenin Equivalent CircuitsImpedance AnalysisPower System ModelingStability LimitsStability Margin AnalysisStability MonitoringThevenin TheoremThevenin's TheoremVoltage Stability
This paper reveals that the impedance match (or the Thevenin circuit) based voltage stability monitoring techniques have problems to predict voltage stability limits when applied to multi-load power systems. Power system loads are nonlinear and dynamic. They cannot be simply represented as Thevenin circuit parameters for impedance match analysis. To overcome these difficulties, a new concept called “coupled single-port circuit” is proposed in this paper. The concept decouples a meshed network into individual single generator versus single bus network and, as a result, a modified version of the impedance match theorem can be used. This leads to a real-time voltage stability monitoring scheme without the need to estimate Thevenin parameters. The scheme can estimate voltage stability margin and identify weak areas in a system based on the SCADA and PMU data. Case studies conducted on several test systems have verified the validity of the proposed method.
23