Short-Circuit Current of Wind Turbines With Doubly Fed Induction Generator

Johan Morren, S.W.H. de Haan

IEEE Transactions on Energy Conversion · 2007 · 534 citations · 11 references

Concepts

TL;DR

Short‑circuit current of wind turbines, particularly those with doubly fed induction generators, has received little attention, despite the common use of crowbar protection on the rotor windings. This paper investigates the short‑circuit behavior, focusing on the short‑circuit current of wind turbines with doubly fed induction generators. The authors first determine the maximum short‑circuit current of a conventional induction machine, then derive approximate equations for a crowbar‑protected doubly fed induction generator, and compare these results with time‑domain simulations. The derived equations predict the short‑circuit current within 15 % of the simulation results.

Abstract

The short-circuit current contribution of wind turbines has not received much attention so far. This paper considers the short-circuit behavior, especially the short-circuit current of wind turbines with a doubly fed induction generator. Mostly, these wind turbines have a crowbar to protect the power electronic converter that is connected to the rotor windings of the induction generator. First, the maximum value of the short-circuit current of a conventional induction machine is determined. The differences between a crowbar-protected doubly fed induction generator and a conventional induction generator are highlighted and approximate equations for the maximum short-circuit current of a doubly fed induction generator are determined. The values obtained in this way are compared to the values obtained from time domain simulations. The differences are less then 15%

References

11