Dielectric strength of oil-immersed transformer insulation with superimposed AC and lightning impulse voltage

Y. Kamata, Kazuhiro Endoh, S. Furukawa, F. Endoh, K. Nonomura, Y. Iwata, Susumu Horiuchi, N. Takasu

IEEE Transactions on Electrical Insulation · 1990 · 20 citations · 2 references

Concepts

Abstract

The 50-Hz AC partial discharge (PD) triggered by a lightning impulse voltage of 1.2/50 mu s and breakdown characteristics under superimposed voltage conditions are studied for several modes of oil-immersed transformer insulation, representing typical combinations of mineral oil and oil-impregnated paper. It is concluded that (1) no AC PD phenomena are triggered by lightning impulse voltage when the preapplied 50-Hz voltage is less than 50% of the RMS value of the AC PD inception voltage for all combinations of polarities, and (2) peak breakdown values of the superimposed voltage are reduced by 10 to 19% for a single applied lightning impulse with a low solid-to-liquid dielectric packing fraction (SLPF) for oil-impregnated paper in the intercoil model, but the difference in breakdown voltage between the superimposed voltage and a single lightning impulse is very small for a high SLPF for oil-impregnated paper, i.e. above about 30%.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">&gt;</ETX>