Enhanced heat transfer/Journal of enhanced heat transfer · 2003 · 26 citations · 0 references
EngineeringMechanical EngineeringHeat TransferThermal AnalysisThermodynamicsHeat ExchangeHeat ExchangersHeat FlowHeat Transfer AnalysisHeat Transfer FundamentalsHeat Transfer In FluidsFriction FactorHeat Exchanger DesignHeat Exchanger EfficiencyHeat Exchanger PerformanceHeat Exchanger Performance AnalysisHeat Transfer MechanismsNusselt NumberPlate Heat Exchangers
Two important variables in plate heat exchanger design are the size (i.e., height H and pitch P) and the orientation (b) of the corrugation embossed on the plates. In this article, the effects of b on the thermal performance of and pressure loss in such an exchanger are investigated through laboratory experimentation for a single-phase application using water. Two rectangular test heat exchangers made from corrugated plates (P = 25 mm and H = 5.5 mm) with b = 45° and 60° were tested. The results showed that the Nusselt number (Nu) and the Darcy friction factor (f) for the 60° channel were higher compared to the 45° sample by a factor of 1.5–2 in the Reynolds (Re) number range 300 < Re < 1700. However, in comparison with a flat plate channel, this factor at Re @ 1000 was of the order of 5 for Nu and as high as 30 for f. Also, the data showed a transitory behavior in the range Re @ 450–900 and 600–1300 for the 60° and 45° samples, respectively. The experimental results are compared with published data from the open literature. While good agreement was found with some studies, a large discrepancy with other experimental data was revealed. This discrepancy is explained by either geometric parameters and/or the experimental techniques used. Also, included in the article is a description of the flow pattern in cross-corrugated cavities and its relation to the plate’s surface temperature. It is shown that even at very low flow rates, the fluid movement is generally erratic and random, generating a fully mixed flow in the heat exchanger.