Variable-Frequency Prony Method in the Analysis of Electrical Power Quality

Jarosław Zygarlicki, Janusz Mroczka

Metrology and Measurement Systems · 2012 · 55 citations · 15 references

DOIFull text

Open access

Concepts

Abstract

Variable-Frequency Prony Method in the Analysis of Electrical Power Quality The article presents a new modification of the the least squares Prony method. The so-called variable-frequency Prony method can be a useful tool for estimating parameters of sinusoidal components, which, in the analyzed signal, are characterized by time-dependent frequencies. The authors propose use of the presented method for testing the quality of electric energy. It allows observation of phenomena which, when using traditional methods, are averaged in the analysis window. The proposed modification of least squares Prony method is based on introduction and specific selection of a frequency matrix. This matrix represents frequencies of estimated components and their variability in time.

References

15