Emissivity of Weathered Conductors After Service in Rural and Industrial Environments

W. S. Rigdon, H. House, R. J. Grosh, W. B. Cottingham

Transactions of the American Institute of Electrical Engineers Part III Power Apparatus and Systems · 1962 · 18 citations · 2 references

Concepts

Abstract

It has been recognized for many years that well-weathered conductors, after being energized for a period of time, have a dark surface resulting in an emissivity sometimes as high as 0.98, whereas a new conductor has an emissivity of approximately 0.23. The length of time needed to develop a high emissivity with the consequent higher current capability is of interest. Samples from various parts of the United States, with the time of service been collected and the emissivity determined. A conductor energized at 500 kv for 1 year at Leadville, Colo., at an altitude of 10,500 feet above sea level, had the same emissivity, 0.23, as a new conductor.

References

2