Dynamic Characteristics of a 22.9 kV Hybrid SFCL for Short-Circuit Test Considering a Simple Coordination of Protection System in Distribution Networks
15
Citations
8
References
2011
Year
Electrical EngineeringReliability EngineeringKv Hybrid SfclEngineeringSmart GridPower System ReliabilityElectric Power DistributionComputer EngineeringElectric Power TransmissionDynamic CharacteristicsPower ElectronicsPower System ProtectionKepco Test GridPower NetworkHybrid SfclSame SfclProtection System
This paper presents the results of short-circuit tests with a 22.9 kV hybrid superconducting fault current limiter (SFCL) on the KEPCO test grid. The hybrid SFCL we used for the test had suffered from lots of field tests including a long term operation and it is still in working order. We have already proved that the SFCL showed high reliability as well as feasibility through a long term operation and short-circuit tests performed before. In this paper, we tried to study a dynamic characteristics of the same SFCL on the distribution power grid through short-circuit tests with a circuit breaker and a reclosing relay. An artificial fault generator (AFG) was used to generate fault currents in the KEPCO power test center. The two objectives of the tests are (1) verifying a precise reaction of the SFCL to reclosing operation and (2) a study for protection coordination with SFCL. The test results showed that the SFCL worked precisely with a fast recovery of the superconducting elements when we applied a one-time reclosing operation with the interval of 0.6 second. We also suggested a proper manipulation of the coordination of the protection system in distribution networks with the SFCL in the paper.
| Year | Citations | |
|---|---|---|
Page 1
Page 1